CVE-2020-28388 | Date: (C)2021-02-11 (M)2023-12-22 |
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.
CVSS Score and Metrics +CVSS Score and Metrics -CVSS V3 Severity: | CVSS V2 Severity: |
CVSS Score : 5.3 | CVSS Score : 5.0 |
Exploit Score: 3.9 | Exploit Score: 10.0 |
Impact Score: 1.4 | Impact Score: 2.9 |
|
CVSS V3 Metrics: | CVSS V2 Metrics: |
Attack Vector: NETWORK | Access Vector: NETWORK |
Attack Complexity: LOW | Access Complexity: LOW |
Privileges Required: NONE | Authentication: NONE |
User Interaction: NONE | Confidentiality: NONE |
Scope: UNCHANGED | Integrity: PARTIAL |
Confidentiality: NONE | Availability: NONE |
Integrity: LOW | |
Availability: NONE | |
| |