[Forgot Password]
Login  Register Subscribe

30479

 
 

423868

 
 

250770

 
 

909

 
 

196157

 
 

282

Paid content will be excluded from the download.


Download | Alert*
CVE
view JSON

CVE-2020-12005Date: (C)2020-06-16   (M)2023-12-22


FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. A vulnerability exists in the communication function that enables users to upload EDS files by FactoryTalk Linx. This may allow an attacker to upload a file with bad compression, consuming all the available CPU resources, leading to a denial-of-service condition.

CVSS Score and Metrics +CVSS Score and Metrics -

CVSS V3 Severity:CVSS V2 Severity:
CVSS Score : 7.5CVSS Score : 7.8
Exploit Score: 3.9Exploit Score: 10.0
Impact Score: 3.6Impact Score: 6.9
 
CVSS V3 Metrics:CVSS V2 Metrics:
Attack Vector: NETWORKAccess Vector: NETWORK
Attack Complexity: LOWAccess Complexity: LOW
Privileges Required: NONEAuthentication: NONE
User Interaction: NONEConfidentiality: NONE
Scope: UNCHANGEDIntegrity: NONE
Confidentiality: NONEAvailability: COMPLETE
Integrity: NONE 
Availability: HIGH 
  
Reference:
https://www.us-cert.gov/ics/advisories/icsa-20-163-02

CPE    1
cpe:/a:rockwellautomation:rslinx_classic
CWE    1
CWE-434
OVAL    1
oval:org.secpod.oval:def:67943

© SecPod Technologies