CVE-2013-6920 | Date: (C)2013-12-09 (M)2023-12-22 |
Siemens SINAMICS S/G controllers with firmware before 4.6.11 do not require authentication for FTP and TELNET sessions, which allows remote attackers to bypass intended access restrictions via TCP traffic to port (1) 21 or (2) 23.
CVSS Score and Metrics +CVSS Score and Metrics -CVSS V2 Severity: |
CVSS Score : 10.0 |
Exploit Score: 10.0 |
Impact Score: 10.0 |
|
CVSS V2 Metrics: |
Access Vector: NETWORK |
Access Complexity: LOW |
Authentication: NONE |
Confidentiality: COMPLETE |
Integrity: COMPLETE |
Availability: COMPLETE |
| |