CVE-2020-15786 | Date: (C)2020-09-10 (M)2023-12-22 |
A vulnerability has been identified in SIMATIC HMI Basic Panels 2nd Generation (incl. SIPLUS variants) (All versions < V16), SIMATIC HMI Comfort Panels (incl. SIPLUS variants) (All versions <= V16), SIMATIC HMI Mobile Panels (All versions <= V16), SIMATIC HMI Unified Comfort Panels (All versions <= V16). Affected devices insufficiently block excessive authentication attempts. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.
CVSS Score and Metrics +CVSS Score and Metrics -CVSS V3 Severity: | CVSS V2 Severity: |
CVSS Score : 9.8 | CVSS Score : 5.0 |
Exploit Score: 3.9 | Exploit Score: 10.0 |
Impact Score: 5.9 | Impact Score: 2.9 |
|
CVSS V3 Metrics: | CVSS V2 Metrics: |
Attack Vector: NETWORK | Access Vector: NETWORK |
Attack Complexity: LOW | Access Complexity: LOW |
Privileges Required: NONE | Authentication: NONE |
User Interaction: NONE | Confidentiality: PARTIAL |
Scope: UNCHANGED | Integrity: NONE |
Confidentiality: HIGH | Availability: NONE |
Integrity: HIGH | |
Availability: HIGH | |
| |