[Forgot Password]
Login  Register Subscribe

30480

 
 

423868

 
 

253164

 
 

909

 
 

197077

 
 

282

Paid content will be excluded from the download.


Download | Alert*
CVE
view JSON

CVE-2019-6820Date: (C)2019-05-24   (M)2023-12-22


A CWE-306: Missing Authentication for Critical Function vulnerability exists which could cause a modification of device IP configuration (IP address, network mask and gateway IP address) when a specific Ethernet frame is received in all versions of: Modicon M100, Modicon M200, Modicon M221, ATV IMC drive controller, Modicon M241, Modicon M251, Modicon M258, Modicon LMC058, Modicon LMC078, PacDrive Eco ,PacDrive Pro, PacDrive Pro2

CVSS Score and Metrics +CVSS Score and Metrics -

CVSS V3 Severity:CVSS V2 Severity:
CVSS Score : 8.2CVSS Score : 6.4
Exploit Score: 3.9Exploit Score: 10.0
Impact Score: 4.2Impact Score: 4.9
 
CVSS V3 Metrics:CVSS V2 Metrics:
Attack Vector: NETWORKAccess Vector: NETWORK
Attack Complexity: LOWAccess Complexity: LOW
Privileges Required: NONEAuthentication: NONE
User Interaction: NONEConfidentiality: NONE
Scope: UNCHANGEDIntegrity: PARTIAL
Confidentiality: NONEAvailability: PARTIAL
Integrity: LOW 
Availability: HIGH 
  
Reference:
https://www.schneider-electric.com/en/download/document/SEVD-2019-134-02/

CWE    1
CWE-306

© SecPod Technologies