[Forgot Password]
Login  Register Subscribe

30479

 
 

423868

 
 

248364

 
 

909

 
 

195388

 
 

282

Paid content will be excluded from the download.


Download | Alert*
CVE
view JSON

CVE-2016-7113Date: (C)2016-09-12   (M)2023-12-22


A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 80/tcp could cause the affected device to go into defect mode.

CVSS Score and Metrics +CVSS Score and Metrics -

CVSS V3 Severity:CVSS V2 Severity:
CVSS Score : 7.5CVSS Score : 7.8
Exploit Score: 3.9Exploit Score: 10.0
Impact Score: 3.6Impact Score: 6.9
 
CVSS V3 Metrics:CVSS V2 Metrics:
Attack Vector: NETWORKAccess Vector: NETWORK
Attack Complexity: LOWAccess Complexity: LOW
Privileges Required: NONEAuthentication: NONE
User Interaction: NONEConfidentiality: NONE
Scope: UNCHANGEDIntegrity: NONE
Confidentiality: NONEAvailability: COMPLETE
Integrity: NONE 
Availability: HIGH 
  
Reference:
BID-92748
BID-99471
http://www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-630413.pdf
https://ics-cert.us-cert.gov/advisories/ICSA-17-187-03
https://www.siemens.com/cert/pool/cert/siemens_security_advisory_SSA-323211.pdf

CWE    1
CWE-399

© SecPod Technologies