CVE-2013-2811Date: (C)2013-11-28   (M)2023-12-22


The (1) Catapult DNP3 I/O driver before 7.2.0.60 and the (2) GE Intelligent Platforms Proficy DNP3 I/O driver before 7.20k, as used in DNPDrv.exe (aka the DNP master station server) in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY and iFIX, allow remote attackers to cause a denial of service (infinite loop) via a crafted DNP3 TCP packet.

CVSS Score and Metrics +CVSS Score and Metrics -

CVSS V2 Severity:
CVSS Score : 7.1
Exploit Score: 8.6
Impact Score: 6.9
 
CVSS V2 Metrics:
Access Vector: NETWORK
Access Complexity: MEDIUM
Authentication: NONE
Confidentiality: NONE
Integrity: NONE
Availability: COMPLETE
  
Reference:
http://ics-cert.us-cert.gov/advisories/ICSA-13-297-01
http://ics-cert.us-cert.gov/advisories/ICSA-13-297-02
http://support.ge-ip.com/support/index?page=kbchannel&id=S:KB15805
http://support.ge-ip.com/support/resources/sites/GE_FANUC_SUPPORT/content/live/KB/15000/KB15805/en_US/GEIP13-04%20Security%20Advisory%20-%20Proficy%20HMI%20SCADA%20DNP3%20Driver%20from%20Catapult%20Software.pdf

CWE    1
CWE-20