CVE-2013-2805Date: (C)2019-04-04   (M)2023-12-22


Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it receives a datagram with an incorrect value in the ���Record Data Size��� field. By sending a datagram to the service over Port 4444/UDP with the ���Record Data Size��� field modified to an oversized value, an attacker could cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to this vulnerability can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599

CVSS Score and Metrics +CVSS Score and Metrics -

CVSS V3 Severity:CVSS V2 Severity:
CVSS Score : 7.5CVSS Score : 7.8
Exploit Score: 3.9Exploit Score: 10.0
Impact Score: 3.6Impact Score: 6.9
 
CVSS V3 Metrics:CVSS V2 Metrics:
Attack Vector: NETWORKAccess Vector: NETWORK
Attack Complexity: LOWAccess Complexity: LOW
Privileges Required: NONEAuthentication: NONE
User Interaction: NONEConfidentiality: NONE
Scope: UNCHANGEDIntegrity: NONE
Confidentiality: NONEAvailability: COMPLETE
Integrity: NONE 
Availability: HIGH 
  
Reference:
https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02

CWE    1
CWE-125

© SecPod Technologies