CVE-2020-15787Date: (C)2020-09-10   (M)2023-12-22


A vulnerability has been identified in SIMATIC HMI Unified Comfort Panels (All versions <= V16). Affected devices insufficiently validate authentication attempts as the information given can be truncated to match only a set number of characters versus the whole provided string. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.

CVSS Score and Metrics +CVSS Score and Metrics -

CVSS V3 Severity:CVSS V2 Severity:
CVSS Score : 9.8CVSS Score : 5.0
Exploit Score: 3.9Exploit Score: 10.0
Impact Score: 5.9Impact Score: 2.9
 
CVSS V3 Metrics:CVSS V2 Metrics:
Attack Vector: NETWORKAccess Vector: NETWORK
Attack Complexity: LOWAccess Complexity: LOW
Privileges Required: NONEAuthentication: NONE
User Interaction: NONEConfidentiality: PARTIAL
Scope: UNCHANGEDIntegrity: NONE
Confidentiality: HIGHAvailability: NONE
Integrity: HIGH 
Availability: HIGH 
  
Reference:
https://cert-portal.siemens.com/productcert/pdf/ssa-542525.pdf